We’re proud to be a leading provider of complete life cycle risk management solutions. From ensuring asset safety and legal compliance with our thorough engineering inspections to driving operational efficiency with our specialist non-destructive testing services, (and much more in between), we’re proud of the long-lasting partnerships we have formed with our customers over the last 160 years, based on the value of our solutions.
Sector
Buildings, Properties and Retail Estate
Location
Canary Wharf, London
Services
Vibration Analysis
Remote Monitoring and Data Services
Working in partnership with a leading facilities management organisation
Overview
A facilities management company based in Canary Wharf, London, was seeking an asset monitoring solution to improve the reliability of their cooling towers mounted on the roof of their office block.
This large office building has a floor area of more than 100,000m2 and the cooling towers are essential as they provide ventilation and air conditioning for the 6,000 people that work inside the building.
The site’s maintenance staff wanted to permanently monitor their key assets and receive email alerts if a threshold was exceeded, making the Ronds wireless system an ideal solution.
The challenge
The solution
The result
The vibration level exceeded the customised threshold, and an email alert was sent to the site’s maintenance team.
The data was quickly reviewed at our Remote Data Centre by our expert analysis team who recommended immediate corrective action.
Upon inspection, it was identified that the fan bearing was not correctly secured, and the maintenance team swiftly resolved this.
A significant resultant reduction in vibration was recorded (see Figure 1).
Figure 1: Vibration readings before and after corrective action.
If the looseness had been allowed to progress, it is likely that the fan element would have impacted the housing which could have resulted in catastrophic damage.
It is estimated that the replacement of the fan and repairs to the mounting structure would have cost £10,000.